Description:
GGD Type Low voltage fixed switchgear is applicable to distribution system of AC 50Hz, rated working voltage of 380V and used to power conversion, distribution and control for power, lighting and distribution equipment.
The switchgear meets the standards IEC60439-1 and GB7251, etc.
Features:
u The form of a universal cabinet, the frame which is assembled by partial welding of 8MF cold-formed steel and matching supply of fixed-point manufacturers guarantee the accuracy and quality of the cabinet.
u Modular design of components shortens manufacturing cycle and increases work efficiency.
u The unique design of the heat sink slot allows the sealed cabinet to form a natural air duct for heat dissipation.
u The golden section design makes the overall appearance beautiful and generous.
u The hinged hinge of the door and the special design of the rubber strip improve the IP grade.
u Connection design between instrument door and cabinet mounting and frame forms complete ground protection circuit.
u The top cover of the cabinet can be removed if needed. The lifting ring on the top is easy to lift and ship.
Technical Parameters:
Items | Unit | Value |
Rated insulation voltage | V | AC660 AC1000 |
Rated working voltage | V | AC380 AC660 |
Horizontal busbar rated current | A | 1250 1600 2000 2500 3200 4000 |
Horizontal busbar peak withstand current(0.1S) | kA | 63 105 176 220 |
Horizontal busbar short-time withstand current(1S) | kA | 30 50 80 100 |
Rated power frequency withstand voltage(1min) | V | 2500 |
Secondary power frequency withstand voltage(1min) | V | 2500 |
Shell IP grade |
| IP30. IP40 |
Shell size |
| Width 600(800.1000) multiply by depth 600(800.1000) multiply by height 2200(1600.1800.2000.etc.) |
Using environment:
u Temperature: Min -5℃~Max+40℃;The average temperature(within 24 hours)≦+35℃;
u Altitude: ≦2000m;
u Relative humidity: ≦50% at a maximum temperature of 40 degrees;Allow a large value at lower temperatures.
u Installation site inclination: ≦ 5°;
Installation location: The place with no severe impact and not enough to expose electrical components to corrosion. Indoor use