The quality of survival, technology and development
Quality for survival, technology for development
GGD Type Low voltage fixed switchgear
GGD Type Low voltage fixed switchgear
GGD Type Low voltage fixed switchgear

Description:

GGD Type Low voltage fixed switchgear is applicable to distribution system of AC 50Hz, rated working voltage of 380V and used to power conversion, distribution and control for power, lighting and distribution equipment.

The switchgear meets the standards IEC60439-1 and GB7251, etc.

Features:

u The form of a universal cabinet, the frame which is assembled by partial welding of 8MF cold-formed steel and matching supply of fixed-point manufacturers guarantee the accuracy and quality of the cabinet.

u Modular design of components shortens manufacturing cycle and increases work efficiency.

u The unique design of the heat sink slot allows the sealed cabinet to form a natural air duct for heat dissipation.

u The golden section design makes the overall appearance beautiful and generous.

u The hinged hinge of the door and the special design of the rubber strip improve the IP grade.

u Connection design between instrument door and cabinet mounting and frame forms complete ground protection circuit.

u The top cover of the cabinet can be removed if needed. The lifting ring on the top is easy to lift and ship.

Technical Parameters:

Items

Unit

Value

Rated insulation voltage

V

AC660   AC1000

Rated working voltage

V

AC380   AC660

Horizontal busbar rated current

A

1250  1600  2000  2500  3200  4000

Horizontal busbar peak withstand current(0.1S)

kA

63  105  176  220

Horizontal busbar short-time withstand current(1S)

kA

30  50  80  100

Rated power frequency withstand voltage(1min)

V

2500

Secondary power frequency withstand voltage(1min)

V

2500

Shell IP grade

 

IP30. IP40

Shell size

 

Width 600(800.1000) multiply by depth 600(800.1000) multiply by height 2200(1600.1800.2000.etc.)

 

Using environment:

u Temperature: Min -5℃~Max+40℃;The average temperature(within 24 hours)≦+35℃;

u Altitude: ≦2000m;

u Relative humidity: ≦50% at a maximum temperature of 40 degrees;Allow a large value at lower temperatures.

u Installation site inclination: ≦ 5°;

Installation location: The place with no severe impact and not enough to expose electrical components to corrosion. Indoor use

Product details